Energy Stress of Surge Arresters Due to Temporary Overvoltages (CROSBI ID 573471)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Filipović-Grčić, Božidar ; Uglešić, Ivo ; Milardić, Viktor ; Xemard, Alain ; Guerrier, Arnaud
engleski
Energy Stress of Surge Arresters Due to Temporary Overvoltages
The paper presents a method for selecting the rated voltage of a metal oxide surge arresters (MOSA) based on the calculation of energy stresses. The electrical behaviour of gapless MOSA under temporary overvoltages (TOV) is important when selecting the rated voltage of MOSA. The study of the appropriate MOSA model is conducted for the evaluation of energy stresses due to TOV. The resistive part of the leakage current was derived from the voltage-current (U-I) characteristic for AC voltage that was gained during the laboratory tests. The MOSA model was implemented in the study of energy stresses of station arresters that are installed at both terminals of a compact upgraded line. By implementing the proposed method MOSA with relatively low protection level can be selected without being overstressed by TOV and thus the overvoltage protection of compact line can be improved.
TOV; MOSA; energy stress; laboratory measurements; compact line; EMTP-RV; rated voltage selection
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
2011.
objavljeno
Podaci o matičnoj publikaciji
International Conference on Power Systems Transients (IPST)
Delft:
Podaci o skupu
International Conference on Power Systems Transients (IPST)
predavanje
14.06.2011-17.06.2011
Delft, Nizozemska