Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults (CROSBI ID 180462)
Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Filipović-Grčić, Božidar ; Filipović-Grčić, Dalibor ; Uglešić, Ivo
engleski
Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults
Transient recovery voltage (TRV) is calculated according to the IEC standards and using the EMTP- ATP software. Modeling of electric arc for the SF6 circuit breaker is presented. Influence of grading capacitors and line bay disposition on the TRV waveform on the side of the line in a 400 kV substation is analyzed for the short-line fault (SLF) conditions. Fault location at which the rate of rise of recovery voltage (RRRV) is the highest was determined using the EMTP-ATP simulations. Results obtained according to the IEC standards and using the EMTP-ATP are compared.
Transient recovery voltage; short-line fault; SF6 circuit breaker; electric arc model; EMTP simulations
Rad spada u kategoriju A jer je objavljen u znanstvenom časopisu koji je zastupljen u SCI– Expanded bazi (NN 84/05.) Journal Impact Factor from JCR Database: 1.364 ; Category Name: ENGINEERING, ELECTRICAL & ELECTRONIC ; Journal Rank in Category: 90 ; Quartile in Category: Q2