Induced Overvoltages on the SF6 Substation Enclosure Caused by Switching (CROSBI ID 184735)

Prilog u časopisu | prethodno priopćenje | međunarodna recenzija

Stjepan Jonjić ; Zoran Baus ; Marinko Barukčić ; Induced Overvoltages on the SF6 Substation Enclosure Caused by Switching // International journal of electrical and computer engineering systems, 2 (2011), 2; 55-65

Podaci o odgovornosti

Stjepan Jonjić ; Zoran Baus ; Marinko Barukčić ;

engleski

Induced Overvoltages on the SF6 Substation Enclosure Caused by Switching

This paper investigates overvoltages on the SF6 substation enclosure caused by the switching operation of the interrupter. The paper analyzes the amplitude and the overvoltage duration on the substation enclosure. Switching overvoltages take part in the everyday drive of HV substations and constitute an undesired phenomenon that may often, beside transient disturbances, lead to undesired cases as well. Electrical discharge in the SF6 gas dielectric, caused by very fast overvoltages, spreads from the place of its occurrence towards all directions within the substation, which on discontinuities (e.g. connection bushings, cable bushings) also includes spreading onto the external side of the enclosure and earthed parts of the substation. Such overvoltages are characterized by a very high frequency for which even low inductances represent very high impedances. This paper is focused on simulation options of the transient connection GIS- overhead line in simulation software. Literature sources provide a fine description of the physical background of the observed phenomena. However, it is difficult to find a model presentation in certain software. Due to this fact, this paper shows possible ways of simulating the GIS-air connection with objects in ATP software.

enclosure voltage ; switching ; transient overvoltages

This work was presented on the scientific- professional symposium “Development of Power Engineering in Croatia“ which was held on 21 October 2011 at the Faculty of Electrical Engineering in Osijek on the occasion of the 150th Anniversary of the Croatian Academy of Sciences and Arts.