Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Evaluation of energy stress on line arresters (CROSBI ID 240540)

Prilog u časopisu | izvorni znanstveni rad

Uglešić, Ivo ; Milardić, Viktor ; Filipović-Grčić, Božidar ; Tokić, Amir Evaluation of energy stress on line arresters // Energija : časopis Hrvatske elektroprivrede, 60 (2011), 30-44

Podaci o odgovornosti

Uglešić, Ivo ; Milardić, Viktor ; Filipović-Grčić, Božidar ; Tokić, Amir

engleski

Evaluation of energy stress on line arresters

Line Surge Arresters (LSAs) are efficient means for the improvement of the lightning performance of transmission lines. Determination of optimal LSA number, location and rating is important for the improvement of the reliability and availability of a transmission system. In selection of the LSA special attention should be paid to their energy stress which depends on complex interactions between the arrester locations, grounding, shielding and the local lightning environment. LSAs experience higher energy stress compared to station arresters, because the incoming surge to a station is limited by insulator flashover on the transmission line and impulse corona. In this paper calculations of energy stresses were carried out for a double-circuit 220 kV line with a single shielding wire. Parametric studies were conducted in which arrester discharge energy was a function of: time to half value of stroke current, number of towers with arresters, footing resistance, span length and angle of power frequency voltage. Arrester energy stress is analyzed in case of stroke to tower and shielding failure. From conducted analysis it can be concluded that energy stress on LSAs is lower for shorter span lengths. Tower footing resistance has only minor effect on the discharge energy. Arrester discharge energy strongly depends on time to half of the stroke current, number of towers with installed arresters and angle of power frequency voltage.

Line surge arrester ; modelling ; energy stress calculations ; double-circuit line ; parametric analysis ; ATP-EMTP simulations

Journal of Energy special issue: Papers from International CIGRÉ Colloquium “Application of line surge arresters in power distribution and transmission systems”

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

60

2011.

30-44

objavljeno

0013-7448

Povezanost rada

Elektrotehnika