Combination of heat pump and coil energy recovery loop in central air-conditioning system (CROSBI ID 484263)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Balen, Igor ; Donjerković, Petar ; Galaso, Ivan Combination of heat pump and coil energy recovery loop in central air-conditioning system // Arab-African Conference for Refrigeration and Air-Conditioning, Conference Proceedings / El Hagar, S.M. (ur.). Kairo: American University in Cairo, 2001. str. 33-45-x

Podaci o odgovornosti

Balen, Igor ; Donjerković, Petar ; Galaso, Ivan

engleski

Combination of heat pump and coil energy recovery loop in central air-conditioning system

Generally, by applying the energy recovery equipment in the air-conditioning systems, heating and cooling energy consumption for the supply air preparation, fuel consumption, size requirements for primary utility equipment, and indirectly the environment pollution (emission of the harmful flue gasses and waste heat of the burning process) are reduced. A coil energy recovery loop is one of the air-to-air sensible heat recovery systems, with seasonally reversible energy transfer. In this paper, hour-by-hour energy analysis of a low-velocity central air-conditioning system with both heat pump and coil energy recovery loop was performed. Simulation model of the complete system, up to the level of secondary equipment load calculation, was developed. The model consists of two integrated parts: calculation of the heat loss and heat gain to the space and determination of the heating and cooling load imposed on the air conditioning system. Calculation procedure is based on the heat balance method combined with first-order conduction transfer functions. Besides the simulation, the measurements on coil energy recovery loop were performed. Differences between the simulation and measurement results were about ±3% or smaller. Energy use results for the system components were presented in the proper graphs and also compared to the results obtained for standard central air-conditioning system and air-conditioning system with heat pump. The results have shown that energy use of the system is decreased up to 30%, compared to the standard system. On the other hand, energy saving of the system with heat pump and coil energy recovery loop working together, compared to the system with only heat pump, isn’t significant for most standard applications.

air-conditioning; coil energy recovery loop; heating and cooling capacity; simulation model; system efficiency

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

33-45-x.

2001.

objavljeno

Podaci o matičnoj publikaciji

Arab-African Conference for Refrigeration and Air-Conditioning, Conference Proceedings

El Hagar, S.M.

Kairo: American University in Cairo

Podaci o skupu

Arab-African Conference for Refrigeration and Air-Conditioning

predavanje

29.04.2001-01.05.2001

Kairo, Egipat

Povezanost rada

Strojarstvo