Sliding Mode Observer-Based Load Angle Estimation for Salient-Pole Wound Rotor Synchronous Generators (CROSBI ID 265397)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Lopac, Nikola ; Bulić, Neven ; Vrkić, Nikša Sliding Mode Observer-Based Load Angle Estimation for Salient-Pole Wound Rotor Synchronous Generators // Energies (Basel), 12 (2019), 9; 1609, 22. doi: 10.3390/en12091609

Podaci o odgovornosti

Lopac, Nikola ; Bulić, Neven ; Vrkić, Nikša

engleski

Sliding Mode Observer-Based Load Angle Estimation for Salient-Pole Wound Rotor Synchronous Generators

Synchronous generator load angle is a fundamental quantity for power system stability assessment, with possible real-time applications in protection and excitation control systems. Commonly used methods of load angle determination require additional measuring equipment, while existing research on load angle estimation for wound rotor synchronous generator has been limited to the estimator based on the generator’s phasor diagram and estimators based on artificial neural networks. In this paper, a load angle estimator for salient-pole wound rotor synchronous generator, based on a simple sliding mode observer (SMO) which utilizes field current, stator voltages, and stator currents measurements, is proposed. The conventional SMO structure is improved with use of hyperbolic tangent sigmoid functions, implementation of the second order low-pass filters accompanied with corresponding phase delay compensation, and introduction of an adaptive observer gain proportional to the measured field current value. Several case studies conducted on a generator connected to a power system suggest that the proposed estimator provides an adequate accuracy during active and reactive power disturbances during stable generator operation, outperforming the classical phasor diagram-based estimator by reducing mean squared error by up to 14.10%, mean absolute error by up to 41.55%, and maximum absolute error by up to 8.81%.

wound rotor synchronous generator ; load angle ; sliding mode observer ; state estimation

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

12 (9)

2019.

1609

22

objavljeno

1996-1073

10.3390/en12091609