Calculation method for fin-and-tube heat exchangers operating with nonuniform airflow (CROSBI ID 681249)

Prilog sa skupa u časopisu | izvorni znanstveni rad | međunarodna recenzija

Blecich, Paolo ; Trp, Anica ; Lenić, Kristian Calculation method for fin-and-tube heat exchangers operating with nonuniform airflow // WIT transactions on ecology and the environment / Tadeu, António (ur.). 2019. str. 13-24 doi: 10.2495/ESUS190021

Podaci o odgovornosti

Blecich, Paolo ; Trp, Anica ; Lenić, Kristian

engleski

Calculation method for fin-and-tube heat exchangers operating with nonuniform airflow

This paper presents a new calculation method for fin-and-tube heat exchangers operating with nonuniform airflow. The calculation method consists of discretizing the heat exchanger tubes into tube elements and applying mass and energy conservation equations. The calculation method is capable of predicting local and overall values of thermal effectiveness, heat transfer rates and fluid outlet temperatures in fin-and-tube heat exchangers subject to airflow nonuniformity. The results of the tube element method are compared against experimental data, and good accordance has been achieved between predicted and measured values. Experimental data is collected for fin-and-tube heat exchangers placed inside an open wind tunnel, where airflow nonuniformity is generated by partially obstructing the entrance cross section. This study revealed that airflow nonuniformity causes effectiveness deterioration in fin-and-tube heat exchangers. The exact value of effectiveness deterioration depends on the heat exchanger dimensionless groups – the number of heat transfer units (NTU) and the heat capacity rate ratio (C*) – as well as on the intensity and orientation of the airflow nonuniformity. The design of the tube-side fluid circuitry, which affects the heat exchanger flow arrangement, also plays a role in the effectiveness deterioration. The tube element method revealed that the effectiveness deterioration increases with the intensity of airflow nonuniformity. For an observed nonuniform airflow profile, the effectiveness deterioration is maximum in heat exchangers with a balanced heat capacity rate ratio (C* = 1) and minimum in evaporators and condensers (C* = 0).

fin-and-tube heat exchanger, airflow nonuniformity, effectiveness deterioration, calculation method

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

13-24.

2019.

nije evidentirano

objavljeno

10.2495/ESUS190021

Podaci o matičnoj publikaciji

WIT transactions on ecology and the environment

Tadeu, António

Coimbra: Wessex Institute of Technology Press

978-1-78466-345-2

1746-448X

1743-3541

Podaci o skupu

8th International conference on Energy and Sustainability

predavanje

03.07.2019-05.07.2019

Coimbra, Portugal

Povezanost rada

Strojarstvo

Poveznice
Indeksiranost