Sensitive turn-to-turn fault protection for power transformers (CROSBI ID 516684)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Gajić, Zoran ; Brnčić, Ivo ; Hillström, Birger ; Ivanković, Igor
engleski
Sensitive turn-to-turn fault protection for power transformers
Three most typical weaknesses of the analogue power transformer differential relays have been: 1. Long operating time in case of heavy internal faults followed by main CT saturation 2. Unwanted operations for external faults and transformer inrush 3. Bad sensitivity for low-level internal faults, such as winding turn-to-turn faults With the introduction of the numerical technology the first two problems could be handled in much better way [4]. However sensitivity for internal winding turn-to-turn faults did not improve much. This paper introduces the new protection principle, which will improve differential relay sensitivity for minor internal turn-to-turn faults. However, the first two classical disadvantages are as well efficiently removed by applying the solution described in the paper.
power transformer; sensitive differential protection; turn-to-turn fault
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
broj referata 11-x.
2005.
objavljeno
Podaci o matičnoj publikaciji
de Mesmaeker, Ivan ; Hindle, Paul
Calgary: CIGRÉ
Podaci o skupu
Joint Meetings of Cigré Study Committee B5 and IEEE Power System Relaying Committee, with the Study Committee B5 Colloquium
predavanje
08.09.2005-16.09.2005
Calgary, Kanada