Tube leakage effect on radiation heat flux in boiler (CROSBI ID 526400)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Duić, Neven ; Bogdan, Željko ; Schneider, Daniel-Rolph ; Šerman, Nikola ; Afgan, Naim
engleski
Tube leakage effect on radiation heat flux in boiler
Early diagnostics of tube leakage in a furnace would help in preventing the failure by planning maintenance. The detection system should be based on the reading of the selected variables which are dependent on the water leakage content in the flue gases. In the vicinity of the tube leakage the concentration of water vapor is increased and heat flux density distribution on the furnace wall changed. The degree of change is measure of the incident. The zone method based mathematical model was developed in order to enable that analysis. The three-dimensional mathematical model describes steady-state behavior of the steam generator furnace. The Monte Carlo method is used to calculate radiative heat transfer between the zones. Radiative properties are obtained by the three-band model. It was shown that the radiative heat flux is sufficiently sensitive to detect the water leakage into the furnace.
boiler tube leakage; Monte Carlo method; numerical simulation; mathematical modeling; combustion chamber; radiation
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1995.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the First International Symposium on Radiation Transfer, Vol. 1
Podaci o skupu
ICHMT International Symposium on Radiative Heat Transfer
predavanje
13.08.1995-18.08.1995
Kuşadası, Turska