Transient Stability Simulation of Industrial Power Plant during Faults on 110 kV Transmission Line (CROSBI ID 539625)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Knežević, Goran ; Marić, Predrag ; Nikolovski, Srete Transient Stability Simulation of Industrial Power Plant during Faults on 110 kV Transmission Line // Proceedings of the 31st International convention on information and communication technology, electronics and microelectronics (MIPRO 2008) = 31. međunarodni skup MIPRO ; sv. III : Computers in technical Systems ; Intelligent Systems = Računala u tehničkim sustavima ; Inteligentni sustavi / Bogunović, Nikola ; Ribarić, Slobodan (ur.). Rijeka: Hrvatska udruga za informacijsku i komunikacijsku tehnologiju, elektroniku i mikroelektroniku - MIPRO, 2008. str. 82-87

Podaci o odgovornosti

Knežević, Goran ; Marić, Predrag ; Nikolovski, Srete

engleski

Transient Stability Simulation of Industrial Power Plant during Faults on 110 kV Transmission Line

The paper presents simulation of transient stability of a 20 MVA generator in the industrial power plant Belišće synchronized with a 110 kV transmission network. Three phase and single line to ground faults were simulated at a 110 kV transmission line using DIgSILENT software. Electromagnetic transients (EMT) module was used to simulate transient stability during the fault and switching process. Operational variables such as generator speed, electrical and mechanical power, frequency, currents and voltages in transmission lines were observed. All input data for transmission lines, transformers, synchronous machines and switching devices are obtained from HEP and Belišće databases. Modeling of the system components by considering a very large number of relevant parameters and constants, as well as using real operational values for each system model has enabled the relative accuracy in representing all the states. Waveforms of transients on the 110 kV transmission lines, generator speeds and rotor angles deviation caused by faults have also been presented.

transient stability; transmission network; synchronous generator; short circuits; computer simulation

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

82-87.

2008.

objavljeno

Podaci o matičnoj publikaciji

Proceedings of the 31st International convention on information and communication technology, electronics and microelectronics (MIPRO 2008) = 31. međunarodni skup MIPRO ; sv. III : Computers in technical Systems ; Intelligent Systems = Računala u tehničkim sustavima ; Inteligentni sustavi

Bogunović, Nikola ; Ribarić, Slobodan

Rijeka: Hrvatska udruga za informacijsku i komunikacijsku tehnologiju, elektroniku i mikroelektroniku - MIPRO

978-953-233-038-0

Podaci o skupu

Međunarodni skup MIPRO (31 ; 2008)

predavanje

26.05.2008-30.05.2008

Rijeka, Hrvatska

Povezanost rada

Elektrotehnika