Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Analysis of grounding electrode dynamic characteristics using FEM (CROSBI ID 144632)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Jurić-Grgić, Ivica ; Lucić, Rino ; Kurtović, Mate Analysis of grounding electrode dynamic characteristics using FEM // International review of civil engineering, 3 (2008), 3; 479-483

Podaci o odgovornosti

Jurić-Grgić, Ivica ; Lucić, Rino ; Kurtović, Mate

engleski

Analysis of grounding electrode dynamic characteristics using FEM

This paper presents an analysis of transient behavior of grounding electrode under the soil ionization effect. The proposed numerical model offers the new approach to the transmission line modeling of a grounding system. The numerical model is based on the finite element method (FEM) applied to the transmission line equations in the time domain. The effect of the soil ionization on the dynamic resistance has been taken into account by dynamic change of the radius of the grounding conductor. Besides the soil ionization effect it will be shown the effect of soil permitivity to the dynamic resistance. The obtained results have been compared to the available experimental results from the literature.

the finite element method; nonlinear transmission line; electromagnetic transients

Rad spada u kategoriju A jer je objavljen u časopisu koji je zastupljen u SCI – Expandedu (NN 84/05.)

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

3 (3)

2008.

479-483

objavljeno

2036-9913

Povezanost rada

Elektrotehnika

Indeksiranost