Time Domain Solution for Transient Response of Transmission Tower Structures and Associated grounding System (CROSBI ID 473526)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Carić, Boris ; Moorthy, Selva ; Nikolovski, Srete ; Šljivac, Damir
engleski
Time Domain Solution for Transient Response of Transmission Tower Structures and Associated grounding System
Transient behavior of transmission towers and associated grounding systems exposed to a lightning surge current having a double exponential pulse waveshape is investigated and analyzed. Frequency domain solutions for electromagnetic fields generated by the network of overhead and buried cylindrical conductors subjected to the thin-wire approximation are derived based on the field theory approach. Once the scalar potentials and electromagnetic fields in the vincinity of the tower have been computed at selected frequencies, the time domain response is obtained using the inverse Fast Fourier Transform. Simulation models are obtained by the use of HIFREQ and FFTSES modules of the CDEGS software package.
transmission tower; grounding systems; transient behavior; lightning surge currents; scalar potentials; electromagnetic fields
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
508-513.
1999.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the Australasian Universities Power Engineering Conference and IEAust electric Energy Conference (AUPEC/EECON '99)
Patterson, Dean
Canterbury: The Northern Territory University
Podaci o skupu
Australasian Universities Power Engineering Conference and IEAust electric Energy Conference
predavanje
26.09.1999-29.09.1999
Darwin, Australija