Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

Correction of Resistance Measurement of Large Grounding Systems (CROSBI ID 86790)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Berberović, Sead ; Boras, Vedran Correction of Resistance Measurement of Large Grounding Systems // European transactions on electrical power, 10 (2000), 2; 105-111

Podaci o odgovornosti

Berberović, Sead ; Boras, Vedran

engleski

Correction of Resistance Measurement of Large Grounding Systems

A method for the systematic error correction which appears at the grounding system resistance measurement by means of an auxiliary current electrode, when the distance between the edge of the groundung system and the center of the current electrode is shorter than the minimum distance required by the standard, is presented in this paper. The systematic error increases with the ratio of the size of the grounding system to its distance from the current electrode. The method for the correction of the systematic error is based on modeling of grounding system and current electrode by hemispheres in uniform and two-layer soil model. The calculation results are presented by diagrams, which are useful for the evaluation of systematic error.

resistance measurements; grounding systems

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

10 (2)

2000.

105-111

objavljeno

1430-144X

Povezanost rada

Elektrotehnika

Indeksiranost