MAGNETIC FIELD IN THE VICINITY OF DISTRIBUTION TRANSFORMERS (CROSBI ID 557143)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Ćućić, Branimir
engleski
MAGNETIC FIELD IN THE VICINITY OF DISTRIBUTION TRANSFORMERS
A quasi-static analysis of an oil-type distribution transformer was described to determine the ambient magnetic field in the surrounding region. Windings and terminals were assumed to be primary sources of the magnetic field. Core and tank of the transformer were modeled by secondary sources (surface current density, surface charge density and eddy current density). In order to find these sources, the system of integral equations was transformed into linear system. Magnetic field was calculated by evaluating volume and surface integrals. The calculated and measured results of the magnetic induction were compared on a 630 kVA transformer. Evaluation of the magnetic induction was made for distribution transformers in the range 50-2500 kVA.
distribution transformer; magnetic field; magnetic induction; integral equations
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1-8.
2009.
nije evidentirano
objavljeno
Podaci o matičnoj publikaciji
1 International Colloquium Transformer Research and Asset Management Cavtat, Croatia, November 12 – 14, 2009
Zagreb:
Podaci o skupu
1 International Colloquium Transformer Research and Asset Management Cavtat, Croatia, November 12 – 14, 2009
predavanje
12.11.2009-14.11.2009
Cavtat, Hrvatska