Accurate and reliable information about the temperature of the synchronous generators excitation winding hot spot is necessary to determine the dynamic limit caused by excitation winding overheating in the PQ diagram. For good estimation of a position and the hot spot temperature it is decided to mount 19 temperature probes on one pole of the 6-pole, 400 kVA, 50 Hz synchronous generator. Due to a large number of the probes and because the probes should be glued with the metal epoxy it was assumed that mounting of the probes will disrupt the temperature field of the excitation winding. To get the answer to this question the excitation winding resistance was measured before and after mounting the probes, in a hot and a cold state. Temperature rise can be estimated if the resistance ratio in the hot and the cold state is known. The paper also addresses the analysis of the measurement accuracy. The result shows that, there is no significant influence on the temperature when mounting the 19 temperature probes which covered 10% of the pole excitation winding surface.

Temperature measurement; AC generators; rotating machine measurements; excitation winding; thermal probes; digital measurements; measurement accuracy; measurement errors

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

8 (5)

2011.

776-784

objavljeno

1934-8975

1934-8983

Povezanost rada

Elektrotehnika