Sensitive turn to turn fault protection for power transformer (CROSBI ID 595645)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Gajić, Zoran ; Brnčić, Ivo ; Hillstrom, Birger ; Mekić, Fahrudin ; Ivanković, Igor
engleski
Sensitive turn to turn fault protection for power transformer
The new protection principle yields a very sensitive protection for low-level turn-to-turn faults. All such faults, which involve around 1% short-circuited turns, can be detected. This low value is limited downwards only by an eventual small amount of the false, “steady-state” negative-sequence currents. The new negative- sequence-current-based sensitive protection is a good complement to the traditional power transformer differential protection, which is based on the well-known bias–differential characteristic.
transformer protection; turn to turn protection; sensitive transformer protection
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
2006.
objavljeno
Podaci o matičnoj publikaciji
Atlanta (GA): Georgia Tech Global Learning&Conference
Podaci o skupu
60th annual Georgia Tech Protective Relaying Conference
predavanje
03.05.2006-05.05.2006
Atlanta (GA), Sjedinjene Američke Države; Gruzija