Induction motor behaviour during voltage instability solved by Unified Power Flow Controller
Behaviour of induction motors during voltage unstable situations is of main concern in this paper. Voltage stability problem is viewed from longer-term time domain response of a composite load model with induction motors being embedded. Instability is alleviated by using Unified Power Flow Controller (UPFC). The UPFC is analysed as the device capable of giving voltage support and/or co-ordinating power flow control action. Sensitivity analysis is applied with respect to characteristic parameters of induction motors. Computational procedure reveals critical motor parameters as well as critical time instant in time domain trajectory. The UPFC is then initiated to simultaneously support bus voltage magnitudes at both sides.
FACTS ; voltage stability ; induction motor sensitivity
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
159-164.
2002.
objavljeno
Podaci o matičnoj publikaciji
IASTED
Lahti: International Association of Science and Technology for Development (IASTED)
Podaci o skupu
The Second IASTED International Conference on Power and Energy Systems EuroPES 2002
predavanje
25.06.2002-28.06.2002
Kreta, Grčka