Analysis of surge arresters failures in the installation of broadcasting transmitter (CROSBI ID 625162)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Milardić, Viktor ; Pavić, Ivica ; Tokić, Amir
engleski
Analysis of surge arresters failures in the installation of broadcasting transmitter
In the operation of the broadcasting transmitter, during a lightning storm, comes to frequent surge arrester failures in the switchgear of the broadcasting transmitter and along the 10 kV supply cable (surge arresters in the cable section boxes). Analysis of lightning strokes to the broadcasting transmitter is given in the paper. EMTP simulation of surge arresters loading was conducted. The energy overload of surge arresters is due to lightning flash with more than one lightning strokes or more lightning flashes in short time. Recommendations were also given for improvement of existing surge protection and reduction the number of surge arresters failures.
broadcasting transmitter; lightning stroke; overheating; surge arrester failure
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
---.
2015.
objavljeno
Podaci o matičnoj publikaciji
International Conference on Power Systems Transients 2015
Uglešić, Ivo
Zagreb: Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu
Podaci o skupu
International Conference on Power Systems Transients (IPST2015)
predavanje
15.06.2015-18.06.2015
Cavtat, Hrvatska