Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Analysis of surge arresters failures in the installation of broadcasting transmitter (CROSBI ID 625162)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Milardić, Viktor ; Pavić, Ivica ; Tokić, Amir Analysis of surge arresters failures in the installation of broadcasting transmitter // International Conference on Power Systems Transients 2015 / Uglešić, Ivo (ur.). Zagreb: Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu, 2015. str. ---

Podaci o odgovornosti

Milardić, Viktor ; Pavić, Ivica ; Tokić, Amir

engleski

Analysis of surge arresters failures in the installation of broadcasting transmitter

In the operation of the broadcasting transmitter, during a lightning storm, comes to frequent surge arrester failures in the switchgear of the broadcasting transmitter and along the 10 kV supply cable (surge arresters in the cable section boxes). Analysis of lightning strokes to the broadcasting transmitter is given in the paper. EMTP simulation of surge arresters loading was conducted. The energy overload of surge arresters is due to lightning flash with more than one lightning strokes or more lightning flashes in short time. Recommendations were also given for improvement of existing surge protection and reduction the number of surge arresters failures.

broadcasting transmitter; lightning stroke; overheating; surge arrester failure

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

---.

2015.

objavljeno

Podaci o matičnoj publikaciji

International Conference on Power Systems Transients 2015

Uglešić, Ivo

Zagreb: Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu

Podaci o skupu

International Conference on Power Systems Transients (IPST2015)

predavanje

15.06.2015-18.06.2015

Cavtat, Hrvatska

Povezanost rada

Elektrotehnika

Poveznice