Statistical and Numerical Analysis of Transformer Oil AC Breakdown (CROSBI ID 633466)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Marković, Mladen ; Radić, Ivanka ; Matun, Vlatka Statistical and Numerical Analysis of Transformer Oil AC Breakdown // Proceedings of the 3rd International Colloquium Transformer Research and Asset Management. Split, 2014

Podaci o odgovornosti

Marković, Mladen ; Radić, Ivanka ; Matun, Vlatka

engleski

Statistical and Numerical Analysis of Transformer Oil AC Breakdown

Transformer oil AC breakdown research is an important part of transformer insulation design. Research presented in this paper consists of statistical and numerical analysis of breakdown data measured in portable oil tester. Statistical analysis is done by modeling measured data as a random process with Gaussian and Weibull probability function. Numerical analysis uses statistical data for calculation of stressed oil volume, stressed electrode area and safety factors of “cumulative stress” method. Both statistical and numerical analysis showed how breakdown withstand depends on different variables and why they are important in measurement interpretation.

oil breakdown; Gaussian distribution; Weibull distribution; FEM; stressed oil volume; stressed electrode area; cumulative stress method

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

2014.

objavljeno

Podaci o matičnoj publikaciji

Podaci o skupu

3rd Internatinal Colloquium Transformer Research and Asset Management

predavanje

15.10.2014-17.10.2014

Cavtat, Hrvatska

Povezanost rada

Elektrotehnika