Analysis of the opposite reactive power direction phenomenon on two parallel overhead transmission lines (CROSBI ID 235179)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Tolić, Ivan ; Nađ, Robert ; Hartmann Tolić, Ivana Analysis of the opposite reactive power direction phenomenon on two parallel overhead transmission lines // Journal of energy technology, 9 (2017), 4; 57-67

Podaci o odgovornosti

Tolić, Ivan ; Nađ, Robert ; Hartmann Tolić, Ivana

engleski

Analysis of the opposite reactive power direction phenomenon on two parallel overhead transmission lines

This paper presents an analysis of the opposite reactive power direction phenomenon on two parallel overhead transmission lines. Measurements are performed on transmission lines, recorded using energy meters. Superficial reasoning leads to the conclusion that the measurement system is not trustworthy. In addition, more detailed theoretical analysis shows that the phenomenon is possible and it is not the result of the incorrect measurement, but it is the result of reactive power distribution along the respective transmission lines.

reactive power, transmission line, measurement