Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

Improving Lightning Location System and Advance Control, Maintenance and Planning of Transmission Power System using Lightning Location System Data (CROSBI ID 652638)

Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija

Stipetić, Nina ; Franc, Bojan ; Uglešić, Ivo ; Mesić, Miroslav ; Ivanković, Igor Improving Lightning Location System and Advance Control, Maintenance and Planning of Transmission Power System using Lightning Location System Data // International Colloquium on Lightning and Power Systems, Ljubljana 2017 / Babuder, Maks ; Pack, Stephan (ur.). Ljubljana: CIGRÉ, 2017. str. 1-10

Podaci o odgovornosti

Stipetić, Nina ; Franc, Bojan ; Uglešić, Ivo ; Mesić, Miroslav ; Ivanković, Igor

engleski

Improving Lightning Location System and Advance Control, Maintenance and Planning of Transmission Power System using Lightning Location System Data

Complete lightning data were collected using lightning locating system (LLS) in Croatia by the Croatian transmission system operator (TSO). The LLS correlation system runs as a part of the National control center’s utility function, collecting lightning data and correlating with network data in real-time. The real-time lightning correlator function relies upon SCADA to acquire network faults, circuit breaker (CB) operations and relay protection data. Geographic information system (GIS) functionality was integrated into the LLS correlation system in order to make the spatial correlation between lightning strokes and network events. Lightning data are available since 2009 and lightning correlated faults data since 2013, providing full eight and four years, respectively, of precise and comprehensive data inputs from LLS, SCADA and GIS systems. Network planning processes are improved by using statistical and spatial analyses results of lightning correlated data as additional inputs for transmission line reconstruction, modernization and designs of new transmission lines. Lightning statistics for the Croatian transmission network will be presented in this paper to prove a context for the lightning related statistics of the observed transmission network. Statistical analyses on lightning correlated data are conducted taking into account 339 transmission lines of 110, 220 and 400 kV, with total length of 8 458 km. Latest improvements of the system will be presented as well as an example of spatial analyses of transmission lines containing critical segments.

Lightning locating systems, transmission power system, power system control, lightning induced faults, correlation, CB operations

paper, S1_3, 114

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o prilogu

1-10.

2017.

objavljeno

Podaci o matičnoj publikaciji

International Colloquium on Lightning and Power Systems, Ljubljana 2017

Babuder, Maks ; Pack, Stephan

Ljubljana: CIGRÉ

Podaci o skupu

International Colloquium on Lightning and Power Systems, ICLPS 2017

predavanje

18.09.2017-20.09.2017

Ljubljana, Slovenija

Povezanost rada

Elektrotehnika