Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

The impact of current, voltage and phase displacement errors on the cross-border energy exchange (CROSBI ID 257706)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Tolić, Ivan ; Miličević, Kruno ; Malarić, Roman The impact of current, voltage and phase displacement errors on the cross-border energy exchange // Measurement, 132 (2019), 330-335. doi: 10.1016/j.measurement.2018.09.014

Podaci o odgovornosti

Tolić, Ivan ; Miličević, Kruno ; Malarić, Roman

engleski

The impact of current, voltage and phase displacement errors on the cross-border energy exchange

Cross-border energy exchange in the electricity market environment requires high quality measurement and accounting procedure considering the fairness in technical and economic sense. In order to fulfill these requirements, the necessary step is to clarify all uncertainty contributions at the metering point and to correct the exchanged energy for corresponding systematic errors. This approach resulted by a mathematical model for energy correction. The model is briefly presented and the sensitivity analysis of the model is performed: the impact of the current, voltage and phase displacement of the measuring transformers, error of the energy meter and voltage drop in voltage measurement circuits to the corrected energy. The presented procedure shows that the voltage drop has the highest impact to the corrected energy.

Cross-border energy exchange ; Measurement uncertainty ; Energy correction ; Sensitivity analysis

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

132

2019.

330-335

objavljeno

0263-2241

1873-412X

10.1016/j.measurement.2018.09.014

Povezanost rada

Elektrotehnika

Poveznice
Indeksiranost