Interruption of small, medium-voltage transformer current with a vacuum circuit breaker (CROSBI ID 678287)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Xemard, Alain ; Jurišić, Bruno ; Rioual, Michel ; Olivier, Arthur ; Selin, Eric
engleski
Interruption of small, medium-voltage transformer current with a vacuum circuit breaker
Vacuum circuit breakers are known to potentially cause voltage escalation when interrupting small currents. Consequently, their installation in electrical systems may require the use of specific means aiming at reducing overvoltages. In this paper, the subject is explored in a configuration of an industrial plant. A medium-voltage transformer is connected to the electrical feeding system using a cable equipped with a breaker on the opposite terminal. The risk of voltage escalation is studied when the transformer loaded with a small inductive load is switched off. The study is conducted with an EMTP-like software program ; a detailed high-frequency model of the transformer is used as well as a VCB model able to represent current chopping and restriking. The protection provided by surge arresters and a filter is also studied
EMTP-like software program, vacuum circuit breaker, current chopping, high frequency transformer model, voltage escalation, insulation coordination
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1-6.
2019.
objavljeno
Podaci o matičnoj publikaciji
Proceedings of the International Conference on Power Systems Transients - IPST, Perpignan, France, 16th – 20th June 2019
Dennetière, Sébastien
Perpignan: IPST
2434-9739
Podaci o skupu
International Conference on Power Systems Transients (IPST 2019)
predavanje
17.06.2019-20.06.2019
Perpignan, Francuska