Surge Protection of Low-Voltage Systems Connected to Overhead Line (CROSBI ID 523380)
Prilog sa skupa u zborniku | izvorni znanstveni rad | međunarodna recenzija
Podaci o odgovornosti
Uglešić, Ivo ; Milardić, Viktor
engleski
Surge Protection of Low-Voltage Systems Connected to Overhead Line
A procedure of choosing the appropriate surge protective device for low-voltage systems is presented. For typical surge protection application an appropriate EMTP model is devised. The energy overload is calculated for a surge protective device following a simulation of the lightning effect. In this way it is possible to determine a required class for a surge protective device in question. The procedure is tested on some typical overhead low-voltage network. According to calculation results and very good service experiences, Class II surge protective devices can be adequately used for service entrance of buildings.
overhead low-voltage network; surge protective device classes; probability of energy overloading; procedure; protected building
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
nije evidentirano
Podaci o prilogu
1086-1091-x.
2006.
objavljeno
Podaci o matičnoj publikaciji
Podaci o skupu
28th Internationl Conference on Lightning Protection
predavanje
18.09.2006-22.09.2006
Kanazawa, Japan